T400N Elite
Bearing Temperature Monitoring System
T4004NV4CAI, T4004NV46CAI

Unique low cost alarm/indicator panel for use with any 4B NTC-type temperature sensors. ADB810, WDB70, and WDB810 series sensors are recommended.

The T400N ELITE is able to accept signals from up to 8 NTC sensors (zones), which are separated into two groups of 4 zones. Each group of sensors is able to cause alarm and shutdown of individual machine when hazardous conditions are detected. There is a total of 2 Alarm and 2 Stop relays. The control unit is housed in a self contained wall mounting enclosure. A test push button on the lid of the control unit provides for full system verification. Alarm and status LEDs provide means of quick location of the alarm condition, and voltage free relay contacts provide separate alarm and shutdown control. An alarm mute push button is provided on the lid of the control unit and additional connections are provided for an external alarm mute functionality. A rotary switch is used to select the temperature alarm value.

T400N Elite - Bearing Temperature Monitoring System
Product Features
  • Monitors up to Eight Temperature Zones
  • Can Monitor Two Separate Machines via 2 x Alarm and 2 x Stop Relays 
  • Selectable Alarm Temperature Level
  • Configurable Alarm and Stop Delays
  • LED Alarm Indication and Power Status
  • Alarm Mute - Automatic Reactivation on New Alarm
  • Test Feature – Externally Controlled Test Facility
  • Dust Hazard Approved​
Electronics Application

Belt Conveyor

Belt Conveyor

Bucket Elevator

Bucket Elevator

Chain Conveyor

Chain Conveyor

Screw Conveyor

Screw Conveyor
Certification

ATEX

ATEX
Bild
ATEX Logo

UKEx

UKEx
Bild

IECEx

IECEx
Bild
IECExv3

CnEx

CnEx
Bild
Nepsi

CSA

CSA
Bild
CSA logo

CE

CE
Bild
CE Logo

Part numbers:

  • T4004NV4CAI - T400 NTC Elite Control Module  -  24 VDC; ATEX and IECEx Zone 21 and Zone 22
  • T4004NV46CAI - T400 NTC Elite Control Module  - 110-240CAV 50/60Hz or 24VDC ATEX and IECEx Zone 22

Options / Accessories:

  • TX400PLCB PLC Relay Board with 8 relays
  • NTC Bearing Sensors (Type WDB or ADB )
     

Technical Specifications:

T4004NV4CAI T4004NV46CAI
Input Supply Voltage 24 VDC (T4004NV4CAI) 120 to 240 VAC or 24 VDC (T4004NV46CAI)
Alarm Relay Contacts Zone 1 - 1 Pole Normally Open - 8 A @ 250 VAC Zone 1 - 1 Pole Normally Open - 8 A @ 250 VAC
Zone 2 - 1 Pole Normally Open - 8 A @ 250 VAC Zone 2 - 1 Pole Normally Open - 8 A @ 250 VAC
Stop Relay Contacts Zone 1 - 1 Pole Normally Open - 8 A @ 250 VAC Zone 1 - 1 Pole Normally Open - 8 A @ 250 VAC
Zone 2 - 1 Pole Normally Open - 8 A @ 250 VAC Zone 2 - 1 Pole Normally Open - 8 A @ 250 VAC
Sensor Inputs Up To 8 NTC Thermistors Up To 8 NTC Thermistors
Sensor Supply 24 VDC - 100 mA Maximum 24 VDC - 100 mA Maximum
Terminals Power: 4 mm^2 - 14 AWG Maximum Power: 4 mm^2 - 14 AWG Maximum
Signals: 2.5 mm^2 - 16 AWG Maximum Signals: 2.5 mm^2 - 16 AWG Maximum
Dimensions (H x W x D) 9.7 x 7.4 x 4 (inches) / 246 x 188 x 102 (mm) 9.7 x 7.4 x 4 (inches) / 246 x 188 x 102 (mm)
Fixing Centres (H x W) 8.75 x 4 (inches) / 222 x 102 (mm) 8.75 x 4 (inches) / 222 x 102 (mm)
Cable Entry 2 Holes x 25mm Dia 2 Holes x 25mm Dia
Weight 3 lbs / 1.3 Kg 3 lbs / 1.3 Kg
LED Status Indicators Green LED - Power Green LED - Power
Green LED - Hot Bearing #1 through #8 Green LED - Hot Bearing #1 through #8
Red LED - Alarm Red LED - Alarm
Push Buttons Mute Mute
Test Test
WARNING WARNING